LED strip voltage drop worked out: a 5 m 12 V run loses 0.64 V and 11% of its light. Max 12V and 24V run lengths per tape, plus four ways to feed long runs.

LED strip voltage drop is the reason the far end of a long run looks grey while the first metre reads bright, and it is a division problem rather than a product problem: the copper inside the tape has resistance, every LED along the run draws its current through that copper, and what arrives at the last metre is the supply voltage minus everything the tape took on the way. A 16.4 ft (5 m) roll of 12 V tape at 9.6 W/m loses 0.64 V by the end of the roll — 5.4 % of its 12 V, which is about 89 % of the light. The same tape on a 24 V bus loses 0.32 V, because it draws half the current.
This page works the arithmetic in full: the closed form, the 12 V versus 24 V comparison, a table of maximum run lengths by watts per metre and copper section, and the four ways to feed a long run. Every number here is printed by the same script that draws the diagrams, the way we treat photometric files, so the tables and the pictures cannot disagree. If your detail needs a fixture rather than tape, our ATRO linear light system is specified with the same arithmetic.

Constant-voltage strip is specified at a bus voltage — 12 V or 24 V DC — and the luminaires on it expect that voltage within a tolerance, typically ±0.5 V on 12 V and ±1 V on 24 V. Voltage drop eats that tolerance. On a long run the far end leaves the band first as light output, then as behaviour: a little colour shift, a lower drive current, and a gradient the client sees before anyone measures it.
| Same 9.6 W/m tape, same 0.62 mm² foil | 12 V | 24 V |
|---|---|---|
| Current at the feed, 16.4 ft (5 m) roll | 4.00 A | 2.00 A |
| Drop at the far end | 0.64 V | 0.32 V |
| Drop as a share of the bus | 5.4 % | 1.3 % |
| Light output at the far end | 89 % | 97 % |
| Longest run inside a 3 % budget | 3.8 ft | 7.6 ft |
| Longest run inside a 5 % budget | 6.4 ft | 12.7 ft |
Read the last two rows against each other. Halving the voltage doubles the current for the same wattage; doubling the current doubles the drop. So 12 V loses the run twice over — once through current, once through a tighter percentage on a smaller number. That is the entire case for 24 V, and none of it is about which voltage is “better”.

A strip is not one load at the end of a cable. It is a load spread along a resistor, and the current falls as it travels: the segment beside the feed carries every watt on the run, the middle carries half, the last few millimetres carry almost nothing. Integrating the out-and-back drop over that falling current gives a closed form.
V(x) = I₀ · ρ · 2 · (L·x − x²/2) / L volts lost at distance x
V(L) = I₀ · ρ · L volts lost at the far end
I₀ total current at the feed = (W/m × L) / V [A]
ρ one conductor, hot = 0.0200 Ω·mm²/m for copper at 60 °C
L run length, feed to far end [m]The factor of two that everyone adds by reflex — out and back — cancels against the
distributed load, so the far end loses I₀ρL, not 2I₀ρL.
Modelling the whole roll as one lumped load at the far end over-states the drop by exactly 2×,
which is a reliable way to reject a layout that was fine.
Run it on the headline case — a 16.4 ft roll of 9.6 W/m tape at 12 V, on 0.62 mm² foil, over 5.00 m:
I₀ = 9.6 × 5.00 / 12 = 4.00 A
ρ = 0.0200 / 0.62 = 0.0322 Ω/m
V(L) = 4.00 × 0.03 × 5.00 = 0.64 V0.64 V off a 12 V bus is 5.4 %. Two rolls on the same feed is not twice the drop, it is four times: 2.57 V, or 21.4 %, because the length doubles and the current feeding that doubled length doubles with it. Ten metres of 12 V tape is not a longer version of five metres; it is a different problem.

Voltage drop matters because LED output is not linear in voltage. Below the knee the light output ratio falls faster than the volts do — an exponent near 2.2 is close enough for specifying — and drive current falls linearly. So the last metre of a starved run is not 48.2 % dimmer. It is about 77 % dimmer, and it shifts colour while it does it.
Three rolls daisy-chained on one 12 V feed is the classic mistake: 49.2 ft of 9.6 W/m tape, 144 W, 5.79 V lost by the far end — 48.2 % — with the last metre at 23 % of spec. Put the same 49.2 ft on 24 V with 20 W/m tape and 1.30 mm² copper and it loses 2.88 V, 12.0 %.
Thermal drift is the second-order effect worth knowing. Published figures use 20 °C resistivity, 0.01724 Ω·mm²/m. A tape at full output sits near 60 °C on the foil, so the resistance rises and the drop is 1.16× the cold arithmetic. Specify at 0.0200 Ω·mm²/m and a run that measures perfectly on the bench will still measure acceptably once it has warmed up.

Turn the formula around and it becomes useful: the longest run whose far end stays inside a budget. Solve for L:
Lᵢ₃ₓ = budget% × V / (W/m × ρ)Two things drive it and nothing else: the watts per metre, which sets the current, and the copper in the tape, which sets resistance per metre. LED count, colour temperature and CRI are not in this arithmetic, which is why two tapes with the same watts per metre and the same foil behave identically however their phosphor is tuned.
| Strip | Bus | W/m | mm²/conductor | 3 % | 5 % | 10 % | 3 %, IP65 |
|---|---|---|---|---|---|---|---|
| 12 V, 2835 60 LED/m | 12 V | 4.8 | 0.62 | 7.6 | 12.7 | 25.5 | 10.5 |
| 12 V, 2835 120 LED/m | 12 V | 9.6 | 0.62 | 3.8 | 6.4 | 12.7 | 5.2 |
| 12 V, COB 320 LED/m | 12 V | 9.6 | 0.90 | 5.6 | 9.3 | 18.5 | 7.6 |
| 12 V, 5050 RGB | 12 V | 14.4 | 1.05 | 4.3 | 7.2 | 14.4 | 5.7 |
| 24 V, 2835 120 LED/m | 24 V | 9.6 | 0.62 | 7.6 | 12.7 | 25.5 | 7.6 |
| 24 V, 2835 168 LED/m | 24 V | 14.4 | 0.86 | 7.1 | 11.8 | 23.6 | 7.1 |
| 24 V, COB 480 LED/m | 24 V | 14.0 | 0.86 | 7.3 | 12.1 | 24.2 | 7.3 |
| 24 V, COB 840 LED/m | 24 V | 20.0 | 1.30 | 7.7 | 12.8 | 25.7 | 9.6 |
| 24 V, high output | 24 V | 60.0 | 4.00 | 7.9 | 13.2 | 26.3 | 10.3 |
Feet, feed to far end, one feed; divide by 3.281 for metres. The IP65 column uses the reduced watts per metre a silicone sleeve actually passes, because the sleeve traps heat and the same tape has to be driven lower.
Two reading notes. The 24 V column is not uniformly better row for row: a 60 W/m tape reaches 7.9 ft at 3 %, shorter than a lazy 12 V 4.8 W/m tape at 7.6 ft. What a higher bus buys is current per watt, and a high-output tape spends it. And the gap between the 3 % and 10 % columns is the whole argument about who owns the loss: at 10 % a 24 V far end sits at 79 % of spec.


Wiring is cheaper than copper. On a 32.8 ft run of 20 W/m 24 V tape (200 W), one feed at one end loses 1.28 V, 5.3 %, and leaves the far end at 89 % of spec.
| Feed arrangement | Drop at the worst point | Light there | What it costs |
|---|---|---|---|
| One feed, one end | 1.28 V — 5.3 % | 89 % | nothing |
| Feed the middle | 0.32 V — 1.3 % | 97 % | one cable, half the length |
| Feed both ends | 0.32 V — 1.3 % | 97 % | one extra cable, full length |
| Loop the far end back | 0.64 V — 2.7 % | 94 % | a return conductor |
The ranking is not intuitive until you look at the exponents. Feeding the middle halves the distance the current travels and halves the current in each half, so the drop falls by 2 × 2 = 4. Feeding both ends does the same from outside in. A loop is worth exactly 2×, because the return path carries the same current as the feed path. None of these change the tape, the driver or the layout — only where the current enters.

Split the run at the feed, not at the power supply. Two 16.4 ft rolls fed from one 24 V driver through two separate cables behave like two short runs; the same two rolls daisy-chained through one cable behave like one 32.8 ft run. The driver does not care what you do; the copper does.

Two effects turn up before the brightness difference does.
Colour shift. An LED driven below its rated current moves in chromaticity, and on warm white tape the shift reads as slightly warmer and slightly greener at the far end. A 3-step MacAdam ellipse is a binning tolerance, not a voltage tolerance: a run that drops 10 % will show a seam no bin can fix, because the two ends are no longer at the same operating point. On a cove or a wall wash, where the tape is seen along its length, this is the first complaint.
Dimming floor. The drop is a fixed fraction of the bus, so it does not scale with the dimming level. The same 48.2 % is taken off at 100 % and at 10 %. At 10 % brightness the far end is not 10 % dimmer than the near end; it is 48.2 % of the level being requested, which in relative terms is far worse. A tape that looks even at full output can look badly graded in the low-level scene the client actually lives in at night.



Three honest limits, because a formula quoted outside its assumptions is worse than no formula.
Constant-current tape is different. A strip with an on-tape constant-current driver, or a higher-voltage system with per-segment regulation, carries plenty of headroom and does not follow this arithmetic. The drop still happens; the LEDs no longer care.
The feed from driver to tape is part of the budget. A 30 ft 2 × 1.0 mm² feed carrying 4 A loses more than the tape does, and it is the cheapest thing on the job to oversize.
Joints and connectors are resistance too. Every solder joint, clip and mid-run connector adds milliohms and a long-term failure point. A run specified to 4.5 % of a 5 % budget has no room for a bad joint; specify to 3 % and let the joints eat the margin.


If the detail still does not close, the last lever is measurement rather than arithmetic. A meter across the far end under load tells you the whole chain at once — tape, joints and feeder cable.

On a track installation the conductors are busbars in an extrusion, sized for tens of amps, and every head is a short branch off them. On tape the conductor is a foil printed on the same flex as the LEDs — a fraction of a square millimetre — carrying the entire load. That is the whole difference: the tape is its own feeder.
The same physics shows up on magnetic rails, where the same three numbers set the answer: current, conductor, length. If you are weighing a tape detail against a track or linear fixture on the same ceiling, our notes on magnetic track lighting and on track light spacing use the same units and the same budget.

Tape is right when the light belongs in a 25 mm slot. When the run is long, visible, or needs a serviceable driver, a linear fixture puts the same LED platform in an extrusion with a real conductor and a defined feed point — the same arithmetic with a much larger section.
Our ATRO linear light system runs 15–50 W with 20°, 40°, 60° and 20°×20° distributions in static white and tunable white, pendant, track-mounted and recessed, so one ceiling can carry the same optics across a 3 ft slot and a 10 ft run. For ceilings that need aimable heads instead of lines, the CADIO track light and the AIMER 25–35 W cover the accent layer, and the track lights category lists the range. Every one ships with a photometric file, so run length gets answered by a curve rather than a catalogue claim.


Send the run length, the watts per metre and where the driver can live, and we will return the drop calculation with the fixture or tape that fits it: request a specification.


On 9.6 W/m tape with 0.62 mm² conductors a 3 % budget is reached at 3.8 ft and a 5 % budget at 6.4 ft. A 16.4 ft roll of the same tape already loses 0.64 V (5.4 %) at the far end. Lighter 4.8 W/m tape reaches 12.7 ft at 5 %.
At the same wattage, 24 V draws half the current, so the drop halves and the usable run doubles: 9.6 W/m tape on the same 0.62 mm² foil reaches 12.7 ft at 5 % on 24 V against 6.4 ft on 12 V. “Better” is the wrong frame — it is the same arithmetic at half the current.
Three percent of the bus is the working target for run length, five percent is the band most constant-voltage tape is specified inside, and ten percent is where the far end is visibly different at 79 % of spec. Convert the percentage into light output before you accept it; the number alone does not tell you what the client will see.
One driver, yes. One feed, only if the arithmetic allows it: 144 W of 9.6 W/m tape is 12.00 A at 12 V, so the driver needs 15.0 A with 20 % headroom, and the run itself needs a mid feed or a move to 24 V. Driver capacity and voltage drop are two separate checks.
Yes, slightly. An LED driven below rated current shifts in chromaticity, and on warm white tape that reads as a fractional move toward green at the far end. The shift shows before the brightness difference is obvious, which is why cove and wall-wash details fail first.
It depends on watts per metre and copper, not on the 24 V label. At a 3 % budget, 20 W/m tape with 1.30 mm² conductors reaches 7.7 ft; 60 W/m high-output tape with 4.00 mm² reaches 7.9 ft; and 9.6 W/m tape on 0.62 mm² reaches 7.6 ft. Ask for the section before you ask for the length.
LED strip voltage drop is a division problem you can finish before you order: total watts over bus voltage gives the current, current times resistivity over section gives the resistance per metre, and current times resistance times length gives the volts you will not get back. The end of the run is where the client looks, so spend the budget there — 24 V for length, a mid feed for compromise, 3 % rather than 10 % when the tape is seen along its length, and the hot resistivity rather than the data-sheet figure. If you would rather we did the sum, send the layout and we will size the feed.
The other half of the same calculation — what the tape emits per metre, and how much of it reaches the surface — is in LED strip lumens per meter.
Branch-circuit voltage drop guidance: IEC 60364-5-52 Annex G (3 % branch, 5 % total). LED output against drive current: US Department of Energy, Solid-State Lighting. Constant-voltage luminaire tolerances and temperature derating: UL Solutions and the ENCORE specification sheets.